Netherlands · Est. 1959

Priva

Blue ID BACnet controllers and Connext BMS for Dutch and Scandinavian building automation

Priva (De Lier, Netherlands, founded 1959) makes building and greenhouse climate control systems — Blue ID BACnet/IP field controllers are the standard for Dutch institutional buildings. KNX module enables hybrid installations with KNX lighting alongside Priva HVAC.

Role in our panels

How we use Priva

The Priva Blue ID controller is the core field device in Priva's building automation range. Available with 36 universal I/O points (configurable as analog input, analog output, digital input, or digital output), the Blue ID communicates on a BACnet/IP LAN network and supports BACnet MS/TP for local field bus connections (actuators, sensors). The Blue ID is programmed using Priva's Flexbuilder engineering tool — a graphical programming environment with pre-built HVAC sequences (VAV, CAV, fan coil, heat pump, chilled beam). The controller handles PI control loops, schedules, and alarm management locally without requiring constant server connectivity. The Blue ID KNX Card is Priva's native KNX integration module for the Blue ID controller. The ETS6 application for the Blue ID KNX Card is downloaded from the Priva Support Portal (priva.com/support). After importing the ETS application into ETS6, the installer configures the Blue ID IP address and selects which BACnet data points to expose as KNX group objects. All tagged BACnet Analog Inputs, Analog Outputs, Binary Values, and Binary Outputs appear as group objects with automatically assigned DPTs. Bidirectional operation: a KNX room thermostat sends measured temperature (DPT 9.001) to a KNX GA → Blue ID KNX Card writes this value to a BACnet Analog Input → Priva heating/cooling PI loop uses this as the measured temperature variable. Conversely, Priva Blue ID calculates valve position (0-100%) → BACnet Analog Output → KNX GA → KNX switching actuator → physical zone valve. Connext is Priva's web-based BMS server platform, replacing the earlier Priva Building Operator (PBO). Connext communicates with Blue ID controllers via BACnet/IP and provides a modern HTML5 dashboard interface accessible from any browser. Connext includes an OPC UA server (port 4840) — the Lingg and Janke KNX Virtual OPC UA Client connects to Connext OPC UA and makes all BACnet data points available as KNX group addresses in ETS6 Virtual. This path is used for supervisory-level BMS integration where real-time bidirectional control is not required (trend logging, setpoint scheduling, energy dashboards). A representative Dutch institutional use case: hospital with 12 floors, each floor having 20 patient rooms. Each floor has one Blue ID with KNX Card controlling fan coil units (Priva HVAC logic) and KNX group addresses for the KNX lighting actuators and pushbutton panels in patient rooms. Connext BMS at hospital level provides ward-by-ward setpoint scheduling, alarm management, and energy monitoring. The ARISTO BewO energy management system receives OPC UA data from Connext for M&T reporting required by Dutch healthcare facility regulations.

Priva Blue ID has an optional KNX module (Blue ID KNX Card) providing native KNXnet/IP integration. ETS6: download Priva ETS application from Priva Support Portal → configure IP address → all BACnet data points tagged for KNX appear as group objects. Bidirectional: KNX room thermostat temperature (DPT 9.001) writes to Priva Blue ID BACnet Analog Input → Priva uses measured value in heating/cooling PI loop. Priva BACnet Binary Output (valve position) writes back to KNX switching actuator → physical valve. Connext BMS: OPC UA Server on port 4840 → Lingg and Janke KNX Virtual OPC UA Client → bidirectional for supervisory control.

Used in these project types

Dutch hospitals — Blue ID + KNX Card for patient room FCU control (Priva) and KNX lighting/blinds (ABB or Jung KNX actuators)
Dutch government buildings — Connext BMS multi-building estate with Building Insight for RGD energy reporting compliance
Scandinavian institutional buildings — Priva specified in Norway and Sweden for university and hospital HVAC automation
Greenhouse horticulture — Priva Process Control for Dutch greenhouse climate (temperature, CO2, humidity) alongside Blue ID for service building HVAC
European educational buildings — Blue ID with KNX Card for classroom FCU control, KNX DALI lighting, and Connext setpoint scheduling

Priva products

Key components we install

PRI-BIDBACnet Controller

Blue ID Controller

36 universal I/O points (configurable AI/AO/DI/DO), BACnet/IP + BACnet MS/TP. DIN rail mount. Programmed in Priva Flexbuilder (graphical HVAC sequences). Blue ID KNX Card slot for native KNX integration. Local micro SD for trend logging and program storage (continuous operation without server). Used as room-level or zone-level HVAC controller in Dutch institutional buildings. Typical application: floor-level controller for 8-12 fan coil units with KNX room temperature inputs.

PRI-TSTRoom Controller

TS Touch

7-inch BACnet touchscreen room controller for conference rooms and individual offices. BACnet/IP. Displays room temperature, setpoint, HVAC mode, and schedule. Not a KNX device — communicates with Blue ID controller via BACnet/IP. For KNX room control alongside Priva HVAC, KNX pushbutton panels handle lighting/blinds while TS Touch manages HVAC. Used in Dutch university meeting rooms and government office individual zones.

PRI-CONNEXTBMS Server

Connext Server

Web-based building supervisor for Priva Blue ID controllers. HTML5 client (no Java, browser-based). BACnet/IP to all Blue ID units on LAN. OPC UA server (port 4840) for KNX Virtual and ARISTO BewO energy management integration. Trend logging (configurable intervals), alarm management (email/SMS), and schedule management for all Blue ID data points. Windows Server VM deployment. Dutch hospital standard BMS platform. Replaces legacy Priva Building Operator (PBO) systems.

PRI-KNXKNX Card

KNX Module

Native ETS6 KNX integration card for Priva Blue ID controller. Plugs into Blue ID expansion slot. Provides KNXnet/IP tunnelling interface on building LAN. ETS6 application from Priva Support Portal. All BACnet data points tagged in Flexbuilder appear as group objects in ETS6. Bidirectional: KNX sensors write to Blue ID; Blue ID actuator outputs write to KNX. No third-party BACnet/KNX gateway required. Eliminates LOYTEC or Intesis gateway cost for Priva-based projects.

PRI-BIEnergy Software

Building Insight

M&T (Monitoring and Targeting) and energy analytics platform. Connects to Connext BMS via OPC UA or direct BACnet. Dutch RGD (Rijksgebouwendienst) and EU Energy Performance Directive compliant reporting. Dashboard with energy benchmarking per m2, setpoint compliance reporting, and fault detection analytics. Used in Dutch government and healthcare portfolios for mandatory energy reporting. SaaS or on-premise deployment.

Priva FAQ

Is Priva used outside the Netherlands?

Yes — Priva is the dominant BMS brand in Netherlands, Belgium, and is strong in Scandinavia and Middle East. In the Netherlands, Priva holds an estimated 40-50% share of institutional building automation (hospitals, universities, government). Norwegian and Swedish healthcare buildings frequently specify Priva due to established installation partner networks. Priva also has a significant greenhouse automation business internationally (Priva Process Control for horticultural climate).

Does Priva Blue ID require a third-party BACnet/KNX gateway?

No — the Blue ID KNX Card provides native integration without external gateway. The KNX Card is Priva's own module (not a third-party product) and is supported directly by Priva technical support. This contrasts with Siemens Desigo or Schneider Electric EcoStruxure, where a third-party LOYTEC or Intesis gateway is required for KNX integration. The Priva KNX Card reduces system complexity and eliminates the gateway as a failure point.

Can Priva handle KNX group addresses directly in Connext BMS?

Via the Blue ID KNX Card, Connext BMS sees all KNX data points as BACnet objects — full M&T and control from Connext. The KNX Card translates KNX group address values into BACnet data points in the Blue ID, which Connext reads via BACnet/IP. From Connext's perspective, all data (HVAC sensor values and KNX lighting/blinds states) appears as BACnet objects. This allows Connext to trend KNX lighting energy data, include KNX blinds state in occupancy reports, and schedule KNX setpoints alongside HVAC from one interface.

Need a panel with Priva components?

We select, procure, assemble and certify. Free initial consultation.

Request consultation →
Loading...