Commercial · KNX · DALI-2 · BACnet · IEC 61439

Corporate Office — KNX Automation

Presence-adaptive lighting that cuts energy by 40%. HVAC integrated with occupancy. MID-certified energy metering per floor. Meeting rooms that configure themselves.

DALI-2 presence-adaptive lighting

The most impactful function in an office: lights on only when someone is there, at the exact level needed. DALI-2 presence control (DALI-2 Part 303 sensors) gives closed-loop control: sensor measures lux level, adjusts DALI ECG output to maintain target illuminance (typically 500 lux on desk per EN 12464-1).

DALI-2 office control strategy:

  • Presence zone: PIR sensor covers 2×2m work area. Occupancy = 500 lux maintained. Empty 10 min = fade to 0%
  • Daylight harvesting: Lux sensor at window. Sunny day → ceiling fixture dims to 20%. Overcast → 80%
  • Groups: Row of desks = one DALI group. Press one switch = full row on/off
  • Scenes: Normal (500 lux), Cleaning (100%), Meeting (dim to 200 lux), Presentation (blind closed + 100 lux accent)
  • Emergency: DALI-2 emergency test via Part 202. Automatic monthly function test, 3h endurance test. Report to BMS

Energy impact:

Office lighting with DALI-2 presence + daylight harvesting typically consumes 35–50% less energy than manually-switched fluorescent/LED circuits. For a 1000 m² office at 15W/m² installed, that's ~6,000 kWh/year saved — significant for energy performance certificates (EPC).

HVAC & BMS integration

In commercial buildings, HVAC is controlled by a Building Management System (BMS — Siemens Desigo CC, Schneider EcoStruxure, Honeywell WEBs). KNX integrates with BMS via BACnet IP or OPC-UA — KNX room-level data (setpoint, occupancy, window contact) feeds the BMS; BMS commands fan coil units, AHUs, and VRV systems.

BACnet IPKNX-BACnet gateway (Loytec L-GATE 902)

KNX → BACnet for Siemens/Honeywell BMS

Modbus TCPKNX-Modbus gateway or WAGO 750-655

Direct integration with VRV outdoor units and AHU controllers

KNX native HVACZennio KLIC-DD fan coil actuator

Direct KNX control of 2-pipe or 4-pipe fan coil units — no BMS needed for small offices

CO₂ sensingSiemens QAX95 DALI+CO₂ room unit

CO₂-triggered ventilation boost — mandatory in meeting rooms (EN 15251)

Meeting room automation

Room booked (via calendar)

Lights on 15 min before meeting. AC target 21°C. Blind to 50% (reduce glare on screen)

Presenter mode

Front lights off. DALI perimeter to 20%. Projector screen drops. Motorised blind closes

Video call mode

Lights 400 lux even distribution. No shadows. Blind 70% (controlled backlight)

Room vacant 15 min

Lights fade off. AC setback 16°C. Blind neutral. Room freed in booking system (webhook)

Investment overview

Small office (500–1000 m²)

KNX switching + DALI-2 presence per zone. No BMS integration. Energy meter per floor.

€8,000–18,000

panel + programming

Mid-size office (1000–3000 m²)

Multi-line KNX, DALI-2 full with daylight harvesting, BACnet/Modbus HVAC, meeting room scenes, MID metering.

€20,000–55,000

panel + programming

Large office fit-out (3000–10000 m²)

Full BMS integration, KNX backbone, multi-floor DALI-2, comprehensive energy monitoring, EPC optimisation.

Custom

panel + programming

IEC 61439-compliant panels for commercial fit-outs

Certified panels, DALI-2 commissioned on-site, BACnet integration tested. Full documentation for building handover — M&E package included.