World's Largest Inverter Manufacturer: SH Hybrid Series with KNX Integration

Sungrow (Hefei, China, with major European offices) is the world's largest solar inverter manufacturer by volume — the SH series hybrid inverters (SH5RT-SH15T) are growing rapidly in the European residential and commercial market due to competitive pricing and strong warranty. Modbus TCP on port 502 with single-register and 32-bit register pairs enables KNX building automation integration.

Role in our panels

How we use Sungrow

SH10RT hybrid inverter (10 kW, three-phase): Modbus TCP port 502, unit ID 1. All registers are 16-bit holding type (FC3), but power values use two consecutive registers as a 32-bit big-endian signed int (read as pair). Key registers: 13009 (daily production, uint16, 0.1 kWh), 13010-13011 (total production, uint32, 0.1 kWh), 13022 (battery SOC, uint16, %), 13023-13024 (battery power, int32, W, positive=charge, negative=discharge), 13028 (battery temperature, int16, 0.1°C), 13033-13034 (AC active power, int32, W, positive=export), 13035-13036 (reactive power, kVAR), 13040 (grid frequency, uint16, 0.1 Hz). SBR192 battery module: 6.9 kWh per module, up to 6 in series (41.4 kWh). Battery data accessible via SH inverter Modbus registers — no separate battery Modbus connection needed. KNX integration: MDT Modbus Gateway (IP address of SH inverter, port 502, unit 1). Read task 1: regs 13033-13034 (AC power, 2 regs int32) every 10s. Read task 2: reg 13022 (SOC) every 60s. DPT mapping: AC power → DPT 9.001 kW (divide by 1000), SOC → DPT 5.001 %. SG Ready: Sungrow SH series has digital input terminals (DI1, DI2) for SG Ready state detection — KNX MDT AKD relay drives DI1/DI2 for off-peak forced battery charge and PV surplus boost. Self-consumption: SH10RT built-in self-consumption mode uses internal CT clamp sensor on grid cable; KNX adds higher-level automation (tariff-based, EV charger coordination, multi-load priority).

Sungrow SH hybrid inverter connects via Modbus TCP (port 502, unit ID 1) to KNX gateway — AC power, battery SOC, and battery power enable self-consumption automation, SG Ready load shifting, and EV charger coordination.

Used in these project types

German residential PV + battery self-consumption
Commercial rooftop 3-phase PV installations
KNX villa with EV charger + solar coordination
School and office buildings with large PV arrays

Sungrow products

Key components we install

SG-SH10RTResidential/commercial hybrid

SH10RT hybrid 10 kW three-phase

10 kW three-phase hybrid inverter. Modbus TCP port 502, unit ID 1. 32-bit register pairs for AC power (13033-13034) and battery power (13023-13024). SG Ready digital inputs DI1/DI2. Supports BYD, PYLON, and Sungrow SBR battery modules. Growing market share in Germany and Netherlands.

SG-SH5RTResidential hybrid

SH5RT hybrid 5 kW single-phase

5 kW single-phase hybrid inverter for residential installations. Same Modbus TCP register map as SH10RT (port 502, unit 1). Suitable for smaller homes with single-phase grid connection. SG Ready DI terminals and same KNX integration approach.

SG-SBR192Battery storage

SBR192 6.9 kWh battery module

6.9 kWh stackable Li-ion battery module. Up to 6 modules in series = 41.4 kWh total capacity. Battery SOC and power data exposed via SH inverter Modbus TCP registers — no separate Modbus connection for the battery. Compatible with SH5RT and SH10RT.

SG-SG250HXCommercial string inverter

SG250HX 250 kW commercial string inverter

250 kW commercial string inverter for large rooftop and ground-mount PV installations. Modbus TCP port 502 for KNX building energy management integration. Suitable for schools, offices, and industrial buildings with large PV arrays.

Sungrow FAQ

Are Sungrow registers 16-bit or 32-bit?

16-bit registers, but energy and power values span TWO consecutive registers as a 32-bit big-endian signed int. Read with FC3 for 2 registers and combine: value = (reg_hi << 16) | reg_lo. For example, AC active power registers 13033-13034: read both with a single FC3 request for 2 registers.

What Modbus TCP port does the Sungrow SH series use?

Port 502 (standard Modbus TCP). Different from KOSTAL PLENTICORE (port 1502) and Huawei FusionSolar (port 6607). Unit ID 1. Confirm in inverter web interface under Settings → Communication → Modbus TCP.

Can I use self-consumption mode without KNX?

Yes — SH10RT has an internal self-consumption mode using a built-in CT clamp sensor on the grid cable. KNX adds multi-device coordination: heat pump SG Ready control, EV charger current throttling, and tariff-based automation (Tibber API integration via Node-RED). KNX does not replace but supplements the inverter's internal self-consumption logic.

Need a panel with Sungrow components?

We select, procure, assemble and certify. Free initial consultation.