Germany (Dortmund) · Est. 1872

Wilo

Stratos MAXO Variable-Speed Circulator — Modbus RTU Integration for KNX BMS

Wilo (Dortmund, Germany, founded 1872) is Europe's second-largest circulator pump manufacturer. The Stratos MAXO intelligent circulator (IE5 ECM motor, AUTOADAPT, built-in differential pressure sensor) integrates with KNX via IF-Module Modbus RTU — enabling pump speed, power, and fault status monitoring for HVAC hydronic circuits. Alternative to Grundfos MAGNA3 at competitive pricing, same Modbus RTU integration chain via MDT or Intesis KNX/Modbus gateway.

Role in our panels

How we use Wilo

The Wilo Stratos MAXO is a high-efficiency circulator pump with IE5 ECM (electronically commutated motor) technology. Available in DN25 to DN50 with power range 0.04–1.5kW, the Stratos MAXO achieves EEI (Energy Efficiency Index) below 0.20 and is ErP 2015 Lot 11 compliant. AUTOADAPT function continuously self-adjusts the pump curve to match actual system hydraulics without manual setpoint configuration. The 3.5-inch LCD display provides on-device status and configuration. The built-in differential pressure sensor eliminates the need for external ΔP transducers — flow rate is calculated from the pump curve and ΔP measurement. The IF-Module (Modbus RTU communication module) slides into the GENIbus expansion slot on the Stratos MAXO pump head without tools. Wiring uses RS-485 A/B/GND terminals on the IF-Module — standard RS-485 3-wire connection to the KNX/Modbus gateway. Modbus address is set via the pump display menu (Extras → Communication → Modbus address, range 1–31). Baud rate is fixed at 9600 baud, 8N1 configuration. For RS-485 bus termination, enable the termination resistor on the last device (120Ω via DIP switch on the IF-Module) when the Stratos MAXO is at the physical end of the RS-485 cable run. The Stratos MAXO Modbus register map provides comprehensive operational data: R1 = setpoint 0–100%, R3 = actual speed in RPM, R5 = current power consumption in W, R7 = differential pressure in kPa, R9 = calculated flow in l/h, R100 = alarm word (bitmask for fault types: overheat, blocked rotor, dry run, communication fault), R200 = cumulative energy counter in kWh. Write registers allow Modbus master control of pump setpoint when the pump is in Remote mode (set via display: Extras → Operating mode → Remote). The MDT SCN-MODBUS.01 KNX/Modbus gateway (RS-485 master, up to 31 slaves, 9600 baud) maps Stratos MAXO registers to KNX group addresses via a signal table configured in ETS6. Typical KNX GA assignments: power consumption (DPT 9.001 2-byte float, kW) for BREEAM energy sub-metering, actual speed percentage (DPT 5.001) for BMS display, fault status (DPT 1.001) for maintenance alarm, and cumulative energy (DPT 13.010 4-byte signed, kWh) for energy dashboard. Predictive maintenance logic in ETS6 or Gira HomeServer triggers a KNX alarm when pump power exceeds nominal by 15% — indicating bearing wear or flow restriction requiring service.

Modbus RTU integration via IF-Module — pump speed, power, differential pressure, flow, and fault status mapped to KNX group addresses for HVAC hydraulic monitoring and BREEAM energy sub-metering.

Used in these project types

Commercial HVAC primary circuits with Stratos MAXO + IF-Module Modbus RTU → MDT KNX gateway for pump power and fault status display on Gira HomeServer BMS
Hotel heating and cooling hydraulics with pump fault KNX alerting — Stratos MAXO fault register mapped to KNX alarm GA for engineering team notification
BREEAM Energy sub-metering via Stratos MAXO kWh counter register mapped to KNX energy metering GA for Part L compliance reporting
Residential heating with Stratos PICO for cost-effective ErP compliance where BMS monitoring is not required
Industrial heat recovery circuits with Stratos MAXO Modbus pump speed control from KNX setpoint GA via MDT gateway Remote mode write register

Wilo products

Key components we install

MAXO-Z-25/0.5-10High-Efficiency Circulator (DN25, Heating/Cooling, IE5)

Wilo Stratos MAXO-Z 25/0.5-10

DN25 high-efficiency circulator for heating and chilled water circuits: IE5 ECM motor, 0.04–0.25kW, EEI<0.20, AUTOADAPT, 3.5-inch display, GENIbus slot for IF-Module Modbus RTU. ErP 2015 compliant. Used in residential and commercial primary heating/cooling hydronic circuits where Modbus RTU KNX integration for power monitoring and fault alerting is required.

MAXO-D-30/0.5-8DHW Hygiene Circulator (DN32, Anti-Legionella Thermal Flush)

Wilo Stratos MAXO-D 30/0.5-8

DN32 domestic hot water hygiene circulator: AUTOADAPT, thermal flushing function (anti-Legionella 70°C flush cycle programmable via display), GENIbus slot for IF-Module. Used in hotels and residential buildings with centralized DHW where hygiene cycle compliance and Modbus monitoring of circulation temperature and pump hours are required for BMS records.

IF-MOD-RTUCommunication Module (RS-485 Modbus RTU, Slide-in GENIbus)

Wilo IF-Module Modbus RTU

Slide-in Modbus RTU communication module for Stratos MAXO (GENIbus slot): RS-485 A/B/GND terminals, Modbus address 1–31 via pump display, 9600 baud 8N1, DIP switch termination resistor (120Ω). Provides read access to speed, power, ΔP, flow, energy counter, and alarm word; write access to setpoint in Remote mode. Required for KNX BMS integration via MDT SCN-MODBUS.01 or Intesis gateway.

PICO-25/1-4Cost-Effective Circulator (DN25, Residential, No BMS)

Wilo Stratos PICO 25/1-4

Entry-level energy-efficient circulator for residential heating: ECM motor, EEI<0.23, automatic proportional pressure control, no display, no communication module. No Modbus or BMS integration. Used in cost-sensitive residential projects where pump efficiency is required but KNX or BMS monitoring is not specified.

Wilo-ConnectorCloud Monitoring Platform (Pump Data, Fault Alerts, Mobile)

Wilo Connector Cloud Monitoring App

Optional cloud monitoring platform for Wilo pumps with built-in connectivity (Stratos MAXO with Wilo-Net module): real-time pump data, fault alert push notifications, energy consumption reports, pump replacement recommendations. Complements KNX BMS integration for field service and maintenance team mobile access. Not a replacement for Modbus KNX integration in commercial BMS.

Wilo FAQ

Wilo Stratos MAXO vs Grundfos MAGNA3 for KNX integration?

Both use Modbus RTU via a slide-in communication module (Wilo IF-Module vs Grundfos CIM 150). The integration chain to KNX is identical: RS-485 → MDT SCN-MODBUS.01 or Intesis gateway → KNX group addresses. The key difference is protocol options: MAGNA3 also supports Modbus TCP (CIM 200 module) and GENIbus; Stratos MAXO is Modbus RTU only (RS-485, no TCP). For BMS projects requiring Modbus TCP over Ethernet backbone, Grundfos MAGNA3 + CIM 200 has an advantage. For standard RS-485 Modbus RTU projects, Stratos MAXO is competitively priced and technically equivalent. IE5 motor efficiency is identical in both.

Can AUTOADAPT and Modbus remote control coexist on the Stratos MAXO?

Yes, with configuration. Enable Remote mode on the pump display (Extras → Operating mode → Remote) to allow Modbus setpoint write commands from the KNX gateway. In Remote mode, AUTOADAPT continues to operate within the boundaries of the Modbus-commanded setpoint — it optimises hydraulic behaviour around the commanded set point rather than disabling entirely. If Modbus communication is lost (cable fault, gateway restart), the pump falls back to the last commanded setpoint (configurable) or to a fixed fallback setpoint — configure the fallback behaviour in the pump display under Communication → Fallback.

How many Wilo Stratos MAXO pumps can be connected to one RS-485 bus?

Up to 31 Stratos MAXO pumps per RS-485 bus segment (Modbus addresses 1–31, 9600 baud). Maximum cable length is 1200m total for the RS-485 bus at 9600 baud with 0.5mm2 shielded twisted-pair cable. Enable the 120Ω termination resistor (DIP switch on IF-Module) only on the last pump on the bus and on the KNX gateway RS-485 port — do not terminate intermediate devices. Connect the cable shield to ground at one end only to avoid ground loops.

Need a panel with Wilo components?

We select, procure, assemble and certify. Free initial consultation.

Request consultation →