Power · Cable Sizing · 10 min read

Power Cable Selection for Lighting and Power Circuits

How to choose the right cable cross-section for every circuit in a KNX panel — current capacity tables, voltage drop, derating, and what changes for LED loads.

Cable types used in KNX panels

NYM-J (H05VV-F equivalent)

Lighting, sockets, fixed appliances

The standard fixed-installation power cable for European buildings. PVC insulation, PVC jacket. Used for all concealed wiring in walls, ceiling voids and conduit. Available 1.5 mm², 2.5 mm², 4 mm², 6 mm².

NYY-J (underground/outdoor)

Underground, outdoor, damp locations

PVC cable with stronger outer jacket for direct burial or outdoor installation. Used for external circuits, underground feeds to outbuildings.

H07RN-F (rubber flexible)

Flexible connections, outdoor sockets

Rubber-insulated flexible cable. Used for connections where the cable is moved (appliances, tool connections) or where PVC would crack in cold temperatures.

LIYY / LiYCY (control cable)

Panel wiring, control signals

Multi-core control cable for 24V/230V control signals in panels. Smaller cross-section (0.25–0.75 mm²), multiple cores. Used for KNX actuator inputs, relay coil wiring.

Current capacity table (NYM-J, single circuit)

Current capacity (ampacity) for NYM-J cable in conduit or enclosed in a wall, installation method B2 per IEC 60364-5-52:

Cross-section1-phase (A)3-phase (A)Typical MCBMax load (1ph)
1.5 mm²16 A13 A10–16 A3.7 kW
2.5 mm²20 A17 A16–20 A4.6 kW
4 mm²25 A23 A25 A5.8 kW
6 mm²32 A29 A32 A7.4 kW
10 mm²40 A36 A40 A9.2 kW
16 mm²52 A47 A50 A12 kW

Values for 230/400V AC, ambient temperature 30°C, PVC cable, installation method B2 (in conduit in wall). Apply derating for higher temperatures or bundled cables.

Voltage drop calculation

IEC 60364-5-52 limits voltage drop to 3% for lighting and 5% for other circuits from the origin of the installation to the final load. For LED strips and sensitive electronics, 3% is the practical maximum.

Formula for single-phase circuits:

ΔU (V) = 2 × L × I × ρ / A

where L = cable length (m), I = current (A), ρ = resistivity (0.0175 for copper), A = cross-section (mm²)

Multiply by 2 for single-phase (outward + return conductor)

Maximum cable length for 3% voltage drop at 230V (single-phase, full current load):

Cross-sectionat 10Aat 16Aat 25A
1.5 mm²49 m31 m20 m
2.5 mm²81 m51 m33 m
4 mm²130 m81 m52 m
6 mm²194 m121 m78 m
10 mm²323 m202 m129 m

Derating for bundled cables

When multiple loaded cables are run together in the same conduit or tray, they share heat and must be derated. Apply the following factors to the single-cable ampacity:

Number of circuitsDerating factorExample: 2.5 mm² capacity
20.8016 A
30.7014 A
4–50.6513 A
6–80.5711.4 A
9–120.5010 A
13–160.459 A

Special considerations for LED circuits

LED drivers and dimmers introduce harmonic currents that don't show up in simple power measurements. A circuit supplying LED drivers may have a true current significantly higher than P/V suggests:

  • Use 1.5 mm² as a minimum for dedicated LED circuits — never share with other loads.
  • For long LED strip runs (10+ metres), always calculate voltage drop — even at 10A, a 30m run on 1.5 mm² drops 4.5% at 12V.
  • For 12V LED strips, prefer 24V strips for long runs: at the same wattage, 24V draws half the current, cutting voltage drop by 75%.
  • LED dimmers (trailing edge, DALI) add harmonic distortion — oversize the cable by one step (use 2.5 mm² where 1.5 mm² would technically suffice).
  • Separate LED driver circuits from high-inrush loads (motors, compressors) to avoid nuisance tripping.

Panel wiring designed to code

Cable sizing, short-circuit protection, voltage drop — all calculated and certified for your project.

Request a quote →
Loading...
Back to top