Heating · UFH · Electrothermal Actuator · PI Control · ETS6 · 10 min read

Underfloor Heating KNX Zone Control: Electrothermal Actuators, Manifold Wiring and PI Control

KNX zone control replaces conventional ON/OFF thermostats with digital setpoint management, PI room temperature control and manifold pump logic — delivering precise temperature regulation per zone and eliminating short-cycling through pulse-width modulated relay switching.

Wet UFH system overview

Wet underfloor heating uses PEX pipe loops embedded in floor screed at 150–200mm spacing. Water at 35–45°C flow temperature (supplied by a heat pump, condensing boiler or mixing valve) circulates through each loop, releasing heat uniformly across the floor surface. Each loop is controlled by an electrothermal actuator (ETA) mounted on the manifold valve — the ETA opens or closes the valve based on the room thermostat signal.

Typical UFH manifold specification

  • 10–15 circuits per manifold (one circuit per room zone)
  • PEX-a pipe 16mm × 2mm, loop length 80–120m per circuit
  • 200mm loop spacing in screed (150mm in bathrooms)
  • 35–45°C flow temperature from mixing valve or heat pump
  • One ETA per manifold port — KNX relay actuator controls all ETAs

KNX UFH vs. conventional thermostats

  • Digital setpoint from KNX room unit or homeserver schedule
  • PI control — smoother temperature, less overshoot than hysteresis
  • Floor sensor overtemperature limit (EN 1264-2: 29°C max)
  • Manifold pump logic: pump only runs when zones demand heat
  • Integration with boiler/HP setpoint via weather compensation

Electrothermal actuator types

Electrothermal actuators use a wax element that expands when heated (by 230V or 24V) to push open or close the manifold valve. Two types exist — Normally Closed (NC) and Normally Open (NO) — with opposite fail-safe behaviour.

ETA typeUnpowered statePowered statePower loss fail-safeTypical use
NC (Normally Closed)Valve closedValve open (heat on)No heat — safe defaultResidential UFH (most common)
NO (Normally Open)Valve open (heat on)Valve closedAll heat on — flood risk in summerCooling circuits where open = cool

Standard ETAs: Danfoss TWA-A NC (24V or 230V), Honeywell MT4-024-NC (24V), Belimo TR24A-SR (modulating, 0-10V for proportional control). For KNX relay actuator output, specify 230V NC ETAs — the relay switches mains voltage to the ETA, opening the valve when the relay closes.

Danfoss TWA-A 230V wiring to MDT relay actuator

The MDT AKD-0824V.01 8-channel relay actuator (16A channels) mounts in the KNX panel. Each channel controls one zone ETA. Wiring uses standard 3-core cable (L, N, PE) from the panel to the manifold junction box.

MDT AKD-0824V.01 channel wiring — 8-zone UFH

Panel terminal block:
  L (230V live) → MDT relay channel 1–8 Common (COM)
  N (neutral)   → Manifold junction box N bus bar
  PE (earth)    → Manifold junction box PE bus bar

Per channel output:
  MDT relay channel N (NO contact) → Danfoss TWA-A Live wire
  TWA-A Neutral wire               → manifold N bus bar

When relay channel N closes:
  230V flows through TWA-A wax element
  Element heats → expands → pushes valve open
  Valve opens within 3 minutes (TWA-A response time)

ETS6 channel configuration:
  Output type: Switch (not blind/shutter)
  GA: 8/4/room_no (heating valve, DPT 1.001)
  Inverted: No (1 = relay closed = valve open = heat on)

For 8 zones: 1× MDT AKD-0824V.01 controls all 8 ETAs

Slow response: Danfoss TWA-A requires up to 3 minutes to fully open after the relay closes (wax element heat-up time). This is normal — do not mistake slow valve response for a wiring fault. The KNX thermostat PI integral accounts for this actuator lag. After power cut, allow 5 minutes for all ETAs to return to their NC (closed) position before testing.

Modulating valve actuator (Belimo TR24A-SR)

For zones above 20m² or high-specification residential projects, modulating (0-10V proportional) UFH valve actuators provide variable flow rate per zone — improving temperature accuracy beyond the on/off capability of NC ETAs.

Belimo TR24A-SR wiring and ETS6 configuration

KNX analogue output module: MDT AMS-0816V.01
  (8-channel analogue output, 0-10V)

Per zone channel wiring:
  MDT analogue output 0-10V+ → Belimo TR24A-SR Y(+) signal
  GND (0V) → Belimo TR24A-SR G0(-) signal
  24VAC → Belimo TR24A-SR power supply

Signal scaling:
  0V  → valve fully closed (0% flow)
  10V → valve fully open (100% flow)

ETS6 group address:
  GA 8/4/zone_no (DPT 5.001, 0–100%)
  → MDT analogue output converts to 0-10V
  PI thermostat heating demand (0–100%) → GA 8/4/zone_no

Cost consideration:
  Belimo TR24A-SR: ~4× cost of Danfoss TWA-A NC
  Justified for zones > 20m² or where ±0.3°C room
  temperature accuracy is required

PI thermostat in ETS6

Proportional-Integral (PI) control eliminates the temperature oscillation and overshoot of simple hysteresis thermostats. UFH has high thermal mass — the screed stores heat, making overshoot the main cause of discomfort. PI control with the correct integral time prevents this.

ETS6 PI parameters for UFH zones

Device options:
  MDT SCN-HCA.02 (heating actuator, integrated PI)
  ABB Logic Module PI function block
  Theben RAMSES 870 KNX room unit (built-in PI)

Recommended PI parameters for wet UFH:
  Proportional gain (Kp): 20% per °C deviation
  Integral time (Ti):     150 minutes
  Control output:         0–100% DPT 5.001 (heating demand)

Output to valve:
  Option A (on/off ETAs):  PWM 15-minute cycle
    Relay closes for (heating demand × 15) minutes per cycle
    Example: 40% demand → relay closed 6 min, open 9 min
    Reduces short-cycling vs. pure hysteresis control

  Option B (modulating):   0–10V analogue output
    Direct proportional valve opening (Belimo TR24A-SR)
    No PWM needed — actuator follows demand signal

Floor sensor limit (EN 1264-2: 29°C max floor surface):
  Enable floor sensor in KNX room unit ETS6 parameters
  Floor sensor input: NTC 10kΩ embedded in screed
  If floor sensor > 29°C → thermostat overrides room
  setpoint and reduces heating demand to 0%

KNX room thermostat sensor placement

Incorrect room sensor placement is the most common cause of UFH zone temperature complaints. The KNX room unit measures the actual room temperature used by the PI controller — placement errors directly affect control accuracy.

Correct placement

  • 1.5m above floor on internal wall
  • Away from heat sources (radiators, appliances)
  • Minimum 1m from any person's regular position
  • Not in direct sunlight or window draught
  • Not in dead air corner behind furniture

Avoid these locations

  • Behind doors (temperature not representative of room)
  • On external walls (cold bridging affects reading)
  • Near supply air diffusers (cool supply air skews reading)
  • Adjacent to TV or AV equipment (heat source)
  • Open-plan areas: use ceiling sensor for large spaces

Manifold pump and mixing valve control

The manifold circulator pump must only run when at least one zone valve is open. Running the pump with all valves closed wastes energy and pressurises the circuit. KNX logic monitors all zone GAs and controls the pump relay accordingly.

Manifold pump logic — MDT Logic Module

Zone GAs: 8/4/0 through 8/4/7 (8-zone apartment)
Pump GA:  8/5/0 (Manifold Pump relay, DPT 1.001)
Relay output → pump contactor 230V coil

Logic:
  IF any of (GA 8/4/0 OR 8/4/1 OR 8/4/2 ... OR 8/4/7) = 1
  THEN GA 8/5/0 = 1 (pump on)

  IF all of (GA 8/4/0 AND 8/4/1 AND 8/4/2 ... AND 8/4/7) = 0
  FOR 3 minutes continuously
  THEN GA 8/5/0 = 0 (pump off — run-on delay elapsed)

Pump run-on timer: 3 minutes after last zone closes
  Purpose: distribute residual heat in pipes and screed
  Prevents thermal shock to pump (sudden stop with hot water)

Mixing valve control:
  KNX 0-10V analogue output → mixing valve actuator (Belimo)
  35°C flow in mild weather → 45°C in cold weather
  Weather compensation GA 8/2/0 (outdoor temp) →
  MDT Logic PI → mixing valve setpoint GA 8/5/1

8-zone apartment commissioning procedure

Commission the UFH KNX system in the following order: room thermostats first, then valve actuators, then pump logic, then flow balance.

StepActionPass criterion
1Download ETS6 PI parameters to all 8 room thermostatsEach thermostat shows correct room temperature reading
2Set each room setpoint 3°C above current temperatureRelay actuator GA = 1; ETA audible click within 3 minutes
3Test pump logic: all zones off → wait 3 minutesPump relay GA = 0 (pump stops after run-on timer)
4Open one zone → verify pump starts within 5 secondsPump GA = 1 immediately when first zone opens
5All zones open at full flow — measure flow per loopBalance manifold circuits to equal flow using manifold flow meters
6Set room temperatures to design setpoints; monitor for 24hAll zones stabilise at setpoint ±0.5°C — no continuous oscillation

Common problems and solutions

Room temperature oscillation (short cycling)

Cause: PI integral time too short. Solution: increase Ti from 60 to 150 minutes in ETS6 room unit parameters. Also reduce Kp to 10%. UFH has very slow thermal response — aggressive PI parameters cause overshoot and hunting.

Zones not heating despite relay GA = 1

Check 1: verify ETS6 relay channel output type = Switch (not Blind/Shutter). Check 2: measure voltage at ETA terminals — should be 230V when relay closed. Check 3: ETA polarity (some ETAs have Live and Neutral marked — connecting reversed prevents operation).

One zone stays open permanently

Most likely cause: ETA wax element stuck (mechanical fault) — replace ETA. Check via ETS6 Group Monitor: if GA = 0 but zone still flows, ETA is stuck open. Alternative cause: KNX telegram stuck at 1 (check Group Monitor for repeated telegrams from thermostat with wrong value).

Floor overheating (floor surface > 29°C)

Verify floor sensor limit is enabled in KNX room unit ETS6 parameters — parameter group "Floor sensor" must be active with maximum 29°C. Check floor sensor resistance against NTC table at room temperature. If sensor reads incorrectly, floor limit will not activate.

Need UFH KNX zone control panels built and commissioned?

We supply relay actuator panels with pre-wired ETA circuits, configure ETS6 PI thermostats and commission manifold pump logic — delivered with zone GA tables and commissioning certificates for each apartment or floor.

Request a quote →
Loading...
Back to top