RCD testing · RCBO · BS 7671 · KNX · Selectivity · 10 min read

RCD and RCBO Testing in KNX Panels: Trip Current, Trip Time and Selectivity Verification

KNX distribution panels contain multiple RCCBs and RCBOs protecting circuits with electronic loads — actuators, SMPS power supplies and capacitive inputs — that behave differently from resistive loads under earth fault conditions. Correct RCD type selection and verified trip performance at commissioning is mandatory under BS 7671 and IEC 60364-6.

Why RCD testing is mandatory

BS 7671 (UK Wiring Regulations) and its European equivalent IEC 60364-6 both require RCD testing as part of initial verification of every new electrical installation. Testing proves that the protection device actually operates within its rated parameters — a mechanically intact RCD that trips outside its rated time or current provides inadequate protection and is a latent life-safety risk.

Protection functions of RCDs

  • 30mA RCD: protection against electric shock (lethal current threshold ~30mA for vulnerable individuals)
  • 100–300mA RCD: fire protection (arcing fault current too low to trip MCB)
  • S-type (selective): upstream device with 200–300ms delay for discrimination
  • Time-delayed RCDs: allow downstream RCDs to clear first

Mandatory test intervals

  • Initial commissioning: 100% of all RCDs and RCBOs
  • Residential: every 6 months (mechanical test button), annual instrument test
  • Commercial and industrial: every 6 months instrument test
  • After any fault event or modification: retest affected circuits

RCD types in KNX panels

RCD type must match the waveform of earth fault current that could occur on the protected circuit. KNX actuators and their associated power supplies produce fault current components that Type AC devices cannot detect — making Type AC RCDs inappropriate for KNX actuator circuits.

RCD typeDetectsKNX application
Type ACSinusoidal AC residual current onlyNot suitable for KNX actuator circuits — cannot detect pulsating DC from switched-mode power supplies
Type AAC + pulsating DC residual currentMinimum type for circuits with KNX switch actuators, DALI drivers, LED power supplies — required by IEC 60755
Type FType A + high-frequency (50Hz–1kHz) residual currentRecommended for KNX circuits with VFD-controlled HVAC motors, variable speed pumps
Type BAC + pulsating DC + smooth DC up to 1000 HzRequired for EV charger circuits, PV inverters, VFD drives — overkill for standard KNX lighting circuits

Specify Type A as the minimum for all KNX circuits: IEC 60755 Amendment 2 (2020) prohibits Type AC RCDs in new installations where the protected circuit contains equipment with electronic components (including KNX actuators). Type A is now the effective minimum for any circuit with a switched-mode power supply, LED driver, or KNX device.

Test instrument and connections

RCD testing requires a dedicated installation tester with RCD test function. The instrument injects a precisely controlled earth fault current and measures the time to trip. Standard multimeters cannot perform this function — they lack the controlled current injection and timing circuitry required.

Test instrument setup and connections

Approved instruments:
  Fluke 1660 series (1662, 1664 FC) — recommended
  Megger MFT1741 / MFT1741+ — recommended
  Seaward Primetest 350 — suitable

Test lead connections:
  L (line) terminal   → line conductor at test point
  PE (earth) terminal → protective earth at test point
  Test point          → typically at socket outlet or
                        load terminal of RCBO

Critical: always test from the FURTHEST POINT of the
circuit (highest earth fault loop impedance Zs) — this
is the worst-case condition for RCD operation.

RCD test mode selection:
  0°  phase angle: positive half-cycle injection (standard)
  180° phase angle: negative half-cycle injection
  BS 7671 requires testing at BOTH phase angles for
  Type A RCDs — some may exhibit different trip times
  depending on fault current waveform phase

BS 7671 Table 41.1 test criteria

BS 7671 Table 41.1 defines the test sequence and acceptance criteria for RCDs. The same criteria are referenced by IEC 60364-6 for continental European installations. All three tests must be performed and recorded for each RCD or RCBO.

RCD test sequence and pass criteria

Test 1 — Half rated current (I△n / 2):
  30mA RCD: inject 15mA
  100mA RCD: inject 50mA
  Pass criterion: NO TRIP in 300ms
  Purpose: verify RCD does not nuisance trip below threshold

Test 2 — Rated current (I△n):
  30mA RCD: inject 30mA → trip in ≤ 300ms
  100mA RCD: inject 100mA → trip in ≤ 300ms
  Pass criterion: TRIP within 300ms
  Record measured trip time (e.g. 42ms)

Test 3 — Five times rated current (5 × I△n):
  30mA RCD: inject 150mA → trip in ≤ 40ms
  100mA RCD: inject 500mA → trip in ≤ 40ms
  Pass criterion: TRIP within 40ms
  Purpose: verify fast clearance for high earth fault currents

Test 4 — Mechanical test button:
  Press test button on RCD face
  Pass criterion: RCD trips and latches open
  Purpose: verify mechanical trip mechanism operable

S-type (time-delayed) RCDs — additional criteria:
  Rated current test: trip time between 130ms and 500ms
  (IEC 61008-1 for S-type RCCBs)
  Ensures S-type clears AFTER standard 30mA RCDs downstream

RCBO additional tests

RCBOs combine residual current protection (RCCB function) with overcurrent protection (MCB function) in a single module. Both protection functions must be verified. The residual current test is identical to RCCB testing — the overcurrent element requires different verification.

RCBO residual current test

Identical to RCCB test procedure. Test RCD part using installation tester RCD test function at I△n/2, I△n, and 5×I△n as for standard RCCBs.

Also verify: earth continuity through the RCBO PE terminal — some RCBO designs have a separate PE terminal that requires a bridging link. Measure continuity between PE in and PE out terminals with a low-resistance ohmmeter. Resistance should be below 0.5Ω.

RCBO overcurrent verification

Do not apply 6× rated current on site to verify overcurrent trip — this is destructive to the RCBO and unsafe without proper current injection equipment.

Instead: verify overcurrent characteristic from manufacturer datasheet (time-current curve). Confirm MCB type (B, C, or D) matches the design specification for the protected circuit type. Document datasheet reference in test record.

Selectivity between upstream and downstream RCDs

Where RCDs are installed at multiple levels (upstream incomer and downstream final circuits), selectivity (discrimination) must be achieved. Without selectivity, a downstream fault trips the upstream incomer RCD, de-energising the entire distribution board rather than just the faulted circuit.

RCD selectivity design and verification

Selective (S-type) design:
  Upstream: 100mA S-type RCCB (time delay 200–300ms)
  Downstream: 30mA standard RCCBs / RCBOs

Selectivity verification test:
  Step 1: Induce 30mA earth fault on a downstream circuit
  Expected: only the downstream 30mA RCBO trips
  Upstream 100mA S-type remains closed
  → Test PASS if only downstream device trips

  Step 2: Induce 100mA fault (via instrument 5×I△n on 30mA RCD)
  Expected: both downstream 30mA RCBO AND upstream S-type trip
  (selective discrimination breaks down at 100mA — both trip)
  → This is acceptable and expected behaviour

  Step 3: Reset downstream RCD, verify upstream S-type reset
  Expected: both reset and circuit restored normally

Selectivity NOT achieved if:
  Upstream S-type trips during 30mA downstream fault
  → cause: S-type has too short a delay or incorrect type
  → remedy: verify S-type is IEC 61008-1 S-classified device

Electronic vs. electromechanical RCDs

Two distinct internal designs of RCD exist with significantly different behaviour characteristics in KNX panel applications. The choice affects reliability, suitability for critical circuits, and nuisance trip behaviour.

Electronic RCDs (VIGI modules)

Examples: Schneider Acti9 VIGI CB, ABB RCQ/RCBO-E modules. Require auxiliary power supply (typically from the line conductor). If the auxiliary power supply fails — power cut, blown fuse, connector fault — the RCD function may be lost or the module may lock in tripped position.

Not suitable for: fire shutters, emergency circuits, UPS-backed critical loads where loss of auxiliary power during a fault is possible.

Electromechanical RCDs

Examples: Schneider iID, Hager CDA series, ABB F200 series. Trip mechanism is a toroidal transformer — operates without auxiliary power supply. Trip energy comes from the fault current itself. Operate normally during supply interruptions and power-up transients.

Specify for: KNX PS640 circuit (prevents nuisance trip during bus startup capacitive inrush), fire shutter circuits, emergency lighting, critical HVAC circuits.

Nuisance tripping in KNX panels

Nuisance RCD tripping is one of the most common commissioning issues in KNX panels. The cause is the capacitive input characteristics of KNX bus power supplies and actuators, which create transient earth fault currents during power-up that can exceed the 30mA RCD trip threshold momentarily.

Nuisance tripping causes and mitigations

Root cause:
  KNX PS640 input capacitance: typically 400µF per TP segment
  On power-up: capacitor charges from mains → brief current spike
  Spike has DC component → Type AC RCD cannot discriminate
  Type A RCD detects DC component → may trip at inrush peak

Mitigation 1: Use Type A RCDs (not Type AC)
  Type A RCDs have higher immunity to capacitive inrush
  compared to Type AC which is sensitive to DC components

Mitigation 2: Interlock relay to sequence KNX PS640 startup
  Delay KNX PS640 energisation by 500ms after main RCD
  settles (use time-delay relay or KNX relay with startup delay)
  By the time PS640 energises, RCD has stabilised

Mitigation 3: Omit 30mA RCCB on KNX PS640 circuit
  Where nuisance tripping persists despite Type A RCDs:
  Install upstream 100mA fire protection RCCB only
  KNX bus cable (YCYM 2×2×0.8mm²) is Class II insulated
  SELV bus voltage (29V DC) — Class II cable provides
  equivalent shock protection for the bus conductors
  (Note: 230V output circuits from KNX actuators still
  need standard 30mA RCBO protection)

Mitigation 4: Electromechanical RCBO for PS640 circuit
  Electromechanical type has longer time constant
  Less sensitive to capacitive transient peaks

Test documentation

BS 7671 requires RCD test results to be recorded on the Schedule of Test Results (part of the Electrical Installation Certificate or Minor Works Certificate). Records must be retained for a minimum of 10 years and provided to the building owner.

Schedule of Test Results — RCD section

For each RCD / RCBO — record:
  Circuit reference (from circuit schedule)
  RCD type: AC / A / F / B
  Rated residual operating current I△n (mA): 30 / 100 / 300
  I△n/2 test result: NO TRIP in 300ms — PASS / FAIL
  I△n trip time (ms): measured value, e.g. "42ms"
  5×I△n trip time (ms): measured value, e.g. "18ms"
  Test button mechanical trip: PASS / FAIL
  Phase angle tested: 0° and 180° (for Type A)
  Overall result: PASS / FAIL

S-type RCDs — additional columns:
  S-type delay trip time at I△n (ms): e.g. "245ms"
  S-type non-trip at 50mA (15ms): PASS / FAIL

Format: IEC 60364-6 Annex C (or BS 7671 equivalent)
Retention: minimum 10 years (commercial), life of installation (residential)
Provided to: building owner, local authority (if required), insurer

Need KNX panels with verified RCD performance and full test documentation?

We commission KNX distribution panels with complete RCD and RCBO testing, selectivity verification, nuisance trip analysis and Schedule of Test Results — fully compliant with BS 7671 and IEC 60364-6.

Request a quote →
Loading...
Back to top