Satel · Alarm · 10 min read

Satel Integra Alarm Panel — Full Guide

How to configure Satel Integra for commercial installations, set up ETHM-1 IP monitoring, and integrate with KNX via the INT-KNX module.

Integra panel range

ModelZonesOutputsUsersPartitionsUse
Integra 242420304Small residential
Integra 323232324Apartment, villa
Integra 646464648Commercial, hotel
Integra 12812812825532Large commercial
Integra 256+25625625632Campus, hospital

Zones can be expanded with INT-E, INT-ADR expander modules. Zones are physical wired inputs (NO/NC contacts + resistors for EOL supervision).

Zone types in Integra

Each zone is individually configured in DLOAD10 software. Key zone types:

0 – Not used

Zone disabled

1 – Delay (entry)

Zone triggers alarm after entry delay — for door detectors with entry route

2 – Entry/exit

Combined entry and exit delay zone

5 – Instant alarm

Immediate alarm — for internal PIRs, glass break detectors

7 – Perimeter

Triggers alarm in Stay (home armed) mode — for external beams, door contacts

12 – 24h tamper

Active regardless of arm status — tamper protection

15 – 24h fire

Always active — fire detector input

17 – Panic

Silent or audible panic — panic button input

19 – 24h technical

Technical alarm — water leak, temperature, power failure

ETHM-1 Plus — IP monitoring and remote access

The ETHM-1 Plus module adds Ethernet connectivity to any Integra panel:

  • INTEGRA CONTROL app (iOS/Android) — arm/disarm, zone status, event log
  • DLOAD10 over IP — remote programming without visiting the site
  • IP monitoring — Contact ID or SIA protocol to monitoring station over TCP/IP
  • HTTP API — webhooks to home automation systems (Fibaro, Loxone, Home Assistant)
  • SATEL Cloud — encrypted remote access without port forwarding

INT-KNX — native KNX integration

The INT-KNX module connects Satel Integra directly to the KNX TP bus. This is the cleanest KNX integration available for any alarm panel:

1

INT-KNX acts as a KNX device on the TP bus — appears in ETS as a standard KNX device

2

Maps Integra zone states to KNX group addresses: motion detected → KNX 1-bit value

3

Maps arm/disarm to KNX: arm-away command from KNX → Integra arms partition

4

Maps outputs to KNX: Integra relay output → KNX status group address

5

Maps Integra alarms to KNX: intrusion alarm → KNX 1-bit alarm flag for visualisation

6

All mapping configured in DLOAD10 + ETS — no third-party server required

With INT-KNX, the KNX system can: trigger lighting scenes on intrusion detection, show zone status on KNX touch panels, arm/disarm the alarm when the last person leaves via KNX presence logic, and integrate alarm events into energy management reporting.

Satel Integra + KNX integration

INT-KNX module configured, ETS group addresses mapped, alarm/KNX scenes commissioned. Part of our security panel service.

Request a quote →